Combustible Gas Detection Alarm System

GP-148

Features

・Easy to read: At-a-glance identificatrion of detection status

・Easy to use: Simple, straightforward operation

・Provides peace of mind even in the event of power outages:

 Built-in UPS allows continuous gas leak monitoring for at

 least three days even during power outages.

 Peace of mind, even during emergencies.

・Permits combined monitoring using gas detectors and

 flame detectors.

・Allows users to select up to 12 detection points.

・Features two contacts. Enables combined use of revolving

 lights and buzzers.

・Ideal for combustible gas leak monitoring at LPG, CNG, and

 H2 filling stations.

GP-148

For overseas users

SH-8661A-SP-230

Sampling method

Suction type/Single type, Diffusion type/Single type, Others

Type of alarm

Gas alarm / fault alarm

Display of alarm

Base unit: Red lamp lit
Indicator unit: Red lamp flashing or lit (after resetting), Continuous buzzer

Explosion protected construction

Non-explosion protection

Power source

100 to 120 V AC or 200 to 240 V AC, (50/60 Hz)
[UPS] Lead storage batteries, 12 V, 2.3 Ah × 2

Dimensions

2-point type: Approx. 305 (W) × 290 (H) × 73 (D) mm
12-point type: Approx. 755 (W) × 290 (H) × 73 (D) mm
Please refer to the catalog for 4,6,8,10 points.

Weight

2-point type: Approx. 3.8 kg
12-point type: Approx. 7.9 kg
Please refer to the catalog for 4,6,8,10 points.

Operating temperature range

-10 to +50 °C (no sudden fluctuations)

Operating humidity range

10 to 90 %RH (no condensation)